Lockout/tagout hardware includes padlocks, tags, hasps, lock stations, and device-specific lockouts for breakers, valves, plugs, and cables. OSHA 1910.147(c)(5) requires each device to be durable, standardized, substantial, and identifiable, and used only for energy control.
The right device for the actual panel, valve, or shared disconnect turns a written procedure into physical protection. This guide covers each hardware family and how to choose and standardize a kit for your plant.
What counts as a lockout/tagout device
OSHA divides the world into energy-isolating devices (the disconnect switch, breaker, valve, or plug that actually stops energy) and lockout/tagout devices (the lock, tag, hasp, or adapter that holds the isolating device in the safe position). Your procedures name the first; your hardware crib stocks the second.
Every lockout/tagout device must be durable, standardized by color, shape, or size, substantial enough to prevent removal without excessive force, and identifiable as belonging to the employee who applied it. Locks and tags are for energy control only, never for toolboxes, gates, or lockers.
| Hardware | What it does | When you need it |
|---|---|---|
| Lockout padlock | Physically holds an isolating device in the safe position | Every isolation point, every lockout |
| Tag | Warns employees and identifies the employee who applied it | With lockout or tagout as required by the employer’s program; tagout on a lockable device requires a full-protection demonstration |
| Hasp | Multi-lock adapter letting several workers lock one point | Two-person jobs and small crews |
| Group lockbox | Holds equipment-lock keys; each worker adds a personal lock | Multi-craft and multi-shift jobs |
| Device-specific lockout | Fits breakers, valves, plugs, cables to make them lockable | Wherever the isolating device has no built-in lock provision |
Locks: the core of the program
Select locks that meet the standard and the employer’s energy-control procedure. Follow the site’s individual and group lockout method so each authorized employee has the required protection and control over their device.
Choose devices suitable for the environment and energy-isolating point. Follow the employer’s device-identification and key-control rules; no material or lock style is a universal choice for every hazard.
Tags, hasps, and lock stations
Tags identify who applied the device and why. They must use a standard print and format, warn against operation (Do Not Operate, Do Not Start), attach with a non-reusable tie that withstands the environment, and survive long enough to outlast the job.
A hasp lets multiple lockout devices secure one energy-isolating device; check its manufacturer-rated capacity and fit. A group lockbox may help manage multiple equipment locks. Follow the employer’s group procedure rather than assuming a particular hardware arrangement is suitable.
Device-specific lockouts: breakers, valves, plugs, cables
Select devices only after identifying the energy-isolating devices in the employer’s equipment assessment. The following are examples; confirm compatibility with the device manufacturer and site procedure:
- Breaker lockouts: clamp-on or pin-type adapters for single and multi-pole breakers in the panels you actually have
- Ball-valve and gate-valve lockouts: sized to your valve handles; measure before ordering
- Plug lockouts: boxes that enclose the plug so equipment cannot be reconnected during service
- Cable lockouts: adjustable cables threading through multiple valves, handles, or disconnects on one machine
- Pneumatic isolation devices: select a compatible device for the actual energy-isolating point. Push buttons and selector switches are control devices, not energy-isolating devices under 1910.147(b).
How to choose and standardize
Walk the plant before buying: list every isolation point type across your machine-specific procedures, note the odd sizes, and kit each department for its actual equipment, not a generic catalog bundle. Standardize one lock color per site (or per craft), one tag format plant-wide, and one station layout everywhere so a transferred tech is never re-learning the system.
Buy for the failure modes: spare locks so nobody ever waits (waiting breeds skipping), spare hasps so pairs never share, and weather-rated tags and ties for washdown and outdoor areas. The cheapest hardware program is the one complete enough that the shortcut never looks tempting.
Device rules that become citations
The standard requires devices to be durable, standardized, substantial, identifiable, and used for energy control only. Follow the employer’s procedure for group protection and device removal. The applying employee ordinarily removes a device; if unavailable, follow 1910.147(e)(3).
For multi-worker jobs, a group lockbox is one method. The employer’s procedure must meet the group requirements in 1910.147(f)(3); do not assume that one supervisor’s lock protects every employee.
Frequently asked questions
Keyed alike vs keyed different: which for LOTO?
Keyed-different (unique key per lock) is the standard for personal lockout locks because each employee controls only their own lock. Keyed-alike sets help equip a team quickly, but every worker still applies and removes only their own lock, shared keys never substitute for personal locks.
Can a tag be used instead of a lock?
If the device cannot be locked out, the employer uses tagout. If it can be locked, the employer must use lockout unless it demonstrates full employee protection for tagout under 1910.147(c)(3) and meets the tagout requirements.
What must LOTO devices meet under OSHA?
Durable, standardized, substantial, and identifiable: they must survive the environment, use one recognizable format, resist removal without excessive force or tools, and identify the employee who applied them. And they may be used for energy control only.
How many locks and hasps should a department stock?
Enough that no worker ever waits or shares: one personal lock (plus a spare) per authorized employee, hasps wherever two or more techs share a disconnect, a group lockbox for crew jobs, and device-specific adapters sized to every isolation point in the department procedures, plus spares.