Lockout Lock Removal: Employee Unavailable and Lost-Key Rules

A lockout or tagout device is normally removed only by the employee who applied it. If that employee is unavailable, 1910.147(e)(3) allows the employer to remove it only under a documented procedure, with training, that provides equivalent safety, verifies the employee is not at the facility, makes all reasonable efforts to contact them, and ensures they know before resuming work.

This guide summarizes the federal standard; each employer must establish the process for its site.

The ordinary rule: the applying employee removes the device

Section 1910.147(e)(3) states that each lockout or tagout device must be removed by the employee who applied it, subject to the employer-directed procedure for an unavailable employee described below. Follow the employer’s procedure before restoring energy.

For group lockout, follow the group procedure and applicable device-removal rules for each authorized employee and the equipment locks.

If the applying employee is unavailable

The standard does not limit this procedure to an emergency or add a “job cannot wait” test. The employer must develop, document, and incorporate specific procedures and training into the energy-control program, demonstrate equivalent safety, and include at least these elements:

  • The employer verifies that the authorized employee who applied the device is not at the facility.
  • The employer makes all reasonable efforts to contact that employee to inform them that the device has been removed.
  • The employer ensures the employee knows the device was removed before the employee resumes work at that facility.
  • Follow any additional safeguards and records in the employer’s documented procedure.

The lost-key routine

Follow the employer’s documented lock-removal procedure. A lost key does not by itself authorize an informal removal or override 1910.147(e)(3):

  • If the employee who applied the device is unavailable, use the employer-directed procedure described above.
  • Follow the employer’s process for replacing the key or lock and documenting changes to lock control.
  • Do not use another employee’s key or remove a device outside the employer’s procedure.

What continuity and out-of-service locks can and cannot do

Employers may use additional devices for equipment status or shift continuity, but those devices do not replace the lockout or tagout protection required for covered servicing. Follow the employer’s written procedure and applicable requirements.

Shift changes are not lock removal

Section 1910.147(f)(4) requires procedures for orderly transfer of lockout or tagout protection during shift or personnel changes. Overlap is one way to maintain continuity; follow the employer’s documented method. See the contractor and shift-change guide.

The records that protect you

The standard requires the employer’s specific removal procedure and training to be documented and incorporated into the energy-control program. Follow the employer’s process for recording a removal and retaining related records; 1910.147(e)(3) does not prescribe the fields in a separate removal log.

Frequently asked questions

Is it legal to cut a lockout lock?

The applying employee ordinarily removes the device. If that employee is unavailable, the employer may direct removal under the specific procedure and training required by 1910.147(e)(3). That procedure must provide equivalent safety and include the required absence, contact, and notice elements. Follow the employer’s process; this FAQ is not authorization to remove a device.

What if an employee forgets their key at end of shift?

Follow the employer’s procedure. If the employee who applied the device is unavailable, removal must meet 1910.147(e)(3), including verification that the employee is not at the facility, reasonable efforts to contact them, and ensuring they know before resuming work.

Can a supervisor remove a worker’s lock?

The applying employee ordinarily removes the device. If that employee is unavailable, the employer may direct removal only through the specific procedure and training in 1910.147(e)(3), which must provide equivalent safety and contain the required safeguards.

What if we cannot reach the employee at all?

Use the employer-directed process in 1910.147(e)(3). The employer must verify the employee is not at the facility, make all reasonable efforts to contact them about removal, and ensure the employee knows before resuming work. Follow the full procedure and training.